Answer in brief
CVE-2026-47710 records a High severity (CVSS 8.2) vulnerability in BACnet Stack: Loop reference to long Structured View description causes stack-buffer-overflow. The current sources do not mark it as known exploited. The current feed maps bacnet-stack/bacnet-stack (generic). Check affected ranges and fixed versions before updating.
Analysis pending evidence review
HOL Guard separates source facts from reviewed analysis. See the methodology.
CVSS is 8.2. The current sources do not mark it as known exploited. Treat this as a source-backed prioritization signal, not a statement about your environment.
Analysis status
Analysis pending evidence review
Factual feed record only; HOL analysis is not approved for indexing. Read the methodology.
The current feed maps bacnet-stack/bacnet-stack (generic). Check affected ranges and fixed versions before updating.
| Package | Affected range | Fixed version |
|---|---|---|
| bacnet-stack/bacnet-stackgeneric | <1.4.4 || <1.5.1 || <1.6.0 | 1.4.4, 1.5.1, 1.6.0 |
Published upstream
Nov 12, 2026
Evidence: source:cvelist:source_dates:source-dates:recordSource modified
Nov 12, 2026
Evidence: source:cvelist:source_dates:source-dates:recordFirst seen by HOL
Nov 12, 2026
BACnet Stack is a BACnet open source protocol stack C library for embedded systems. Prior to versions 1.4.4, 1.5.1, and 1.6.0, a stack-buffer-overflow can be triggered in the current master branch when a Loop object reads a referenced property through its default timer path and the referenced property is OBJECT_STRUCTURED_VIEW / PROP_DESCRIPTION containing a long attacker-controlled string. This issue has been patched in versions 1.4.4, 1.5.1, and 1.6.0.
Quoted source text, attributed separately from HOL analysis.